8.1 Quick Menu Parameters

0-01 Language
Option:
[0]
English
*
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
8
8
[5]
Italiano
[6]
Svenska
[7]
Nederlands
[10] Chinese
[20] Suomi
[22] English US
[27] Greek
[28] Bras.port
[36] Slovenian
[39] Korean
[40] Japanese
[41] Turkish
[42] Trad.Chinese
[43] Bulgarian
[44] Srpski
[45] Romanian
[46] Magyar
[47] Czech
[48] Polski
[49] Russian
[50] Thai
[51] Bahasa
Indonesia
[52] Hrvatski
50
®
VLT
Decentral Drive FCD 302
Function:
Defines display language. The frequency
converter is delivered with 4 different
language packages. English and German
are included in all packages. English
cannot be erased or manipulated.
Part of language packages 1–4
Part of language packages 1–4
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 1
Part of language package 2
Part of language package 1
Part of language package 4
Part of language package 4
Part of language package 4
Part of language package 3
Part of language package 2
Part of language package 2
Part of language package 4
Part of language package 2
Part of language package 3
Part of language package 3
Part of language package 3
Part of language package 3
Part of language package 3
Part of language package 4
Part of language package 3
Part of language package 2
Part of language package 2
Part of language package 3
Danfoss A/S © 11/2016 All rights reserved.
1-20 Motor Power [kW]
Range:
Function:
NOTICE
Size
[ 0.09 -
related
3000.00
*
This parameter cannot be adjusted
kW]
while the motor is running.
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the frequency
converter.
This parameter is visible in the LCP if
parameter 0-03 Regional Settings is set to
[0] International.
1-22 Motor Voltage
Range:
Function:
Size
[ 10 -
Enter the nominal motor voltage
related
1000 V]
according to the motor nameplate
*
data. The default value corresponds to
the nominal rated output of the
frequency converter.
1-23 Motor Frequency
Range:
Function:
NOTICE
Size
[20 -
related
1000
*
From software version 6.72 onwards,
Hz]
the output frequency of the frequency
converter is limited to 590 Hz.
Select the motor frequency value from the
motor nameplate data. If a value other than
50 Hz or 60 Hz is selected, adapt the load-
independent settings in parameter 1-50 Motor
Magnetisation at Zero Speed to
parameter 1-53 Model Shift Frequency. For 87
Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. To run at 87
Hz, adapt parameter 4-13 Motor Speed High
Limit [RPM] and parameter 3-03 Maximum
Reference.
MG04F502