6.4 Status Messages

When the frequency converter is in Status mode, status
messages are generated automatically and appear in the
bottom line of the display (see Illustration 6.2).
6
6
1 Operating mode (see Table 6.2)
2 Reference site (see Table 6.3)
3 Operation status (see Table 6.4)
Illustration 6.2 Status Display
Table 6.2 to Table 6.4 describe the status messages shown.
Off
Auto On
Hand On
Table 6.2 Operating Mode
Remote
Local
Table 6.3 Reference Site
32
VLT
Status
799RPM
7.83A
0.000
53.2%
Auto
Remote
Ramping
Hand
Local
Stop
O
Running
Jogging
.
.
.
Stand by
1
2
3
The frequency converter does not react to any
control signal until [Auto On] or [Hand On] is
pressed.
The frequency converter is controlled from the
control terminals and/or the serial communi-
cation.
Control the frequency converter via the
navigation keys on the LCP. Stop commands,
reset, reversing, DC brake, and other signals
applied to the control terminals override local
control.
The speed reference is given from external
signals, serial communication, or internal
preset references.
The frequency converter uses [Hand On]
control or reference values from the LCP.
Danfoss A/S © 11/2016 All rights reserved.
®
Decentral Drive FCD 302
AC Brake
AMA finish OK
AMA ready
AMA running
Braking
1(1)
36.4kW
Braking max.
Coast
Ctrl. ramp-down [1] Control Ramp-down was selected in
Current High
Current Low
DC Hold
DC Stop
Feedback high
Feedback low
[2] AC brake is selected in parameter 2-10 Brake
Function. The AC brake overmagnetizes the
motor to achieve a controlled slow down.
AMA was carried out successfully.
AMA is ready to start. Press [Hand On] to start.
AMA process is in progress.
The brake chopper is in operation. Generative
energy is absorbed by the brake resistor.
The brake chopper is in operation. The power
limit for the brake resistor defined in
parameter 2-12 Brake Power Limit (kW) has
been reached.
[2] Coast inverse was selected as a function
for a digital input (parameter group 5-1*
Digital Inputs). The corresponding terminal
is not connected.
Coast activated by serial communication.
parameter 14-10 Mains Failure.
The mains voltage is below the value set
in parameter 14-11 Mains Voltage at Mains
Fault at mains fault.
The frequency converter ramps down the
motor using a controlled ramp down.
The frequency converter output current is
above the limit set in parameter 4-51 Warning
Current High.
The frequency converter output current is
below the limit set in parameter 4-52 Warning
Speed Low.
[1] DC hold is selected in
parameter 1-80 Function at Stop, and a stop
command is active. The motor is held by a DC
current set in parameter 2-00 DC Hold/Preheat
Current.
The motor is held with a DC current
(parameter 2-01 DC Brake Current) for a
specified time (parameter 2-02 DC Braking
Time).
The DC brake cut-in speed is reached in
parameter 2-03 DC Brake Cut In Speed
[RPM], and a stop command is active.
[5] DC-brake inverse is selected as a
function for a digital input (parameter
group 5-1* Digital Inputs). The
corresponding terminal is not active.
The DC brake is activated via serial
communication.
The sum of all active feedbacks is above the
feedback limit set in parameter 4-57 Warning
Feedback High.
The sum of all active feedbacks is below the
feedback limit set in parameter 4-56 Warning
Feedback Low.