2.3.2 Output specifications

-Transistor output specifications (For Y0 to Y4)
Number of output
Insulation method
Output type
Rated load voltage
Operating load voltage range
Max. load current
Max. surge current
Output points per common
OFF state leakage current
ON state voltage drop
Response time
External power supply
(For driving internal circuit)
Surge absorber
Operation indicator
Internal circuit diagram
- Relay output specifications (Y5)
Item
Number of output
Output type
Rated control capacity
Output points per common
Response time
Life time
Surge absorber
Operation indicator
Note1) Resistance load
Note2) Open/Close frequency: 20 times/min (at the rated control capacity)
Internal circuit diagram
2-8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Item
OFF to ON
ON to OFF
Voltage
Current
1 point
Normally open (1 Form A)
2 A 250 V AC, 2 A 30 V DC
1point/common
OFF to ON
Approx. 10 ms
ON to OFF
Approx. 8 ms
Mechanical
Min. 20,000,000 operations
Electrical
Min. 100,000 operations (resistive load)
None
LCD display (I/O monitor mode)
Description (NPN)
5 points
Optical coupler
Open collector
5 to 24 V DC
4.75 to 26.4 V DC
0.5 A
1 A
5 points/common
100 µA or less
1.5 V or less
50 µs or less (For Y0 and Y1)
1 ms or less (For Y2,Y3 and Y4)
50 µs or less (For Y0 and Y1)
1 ms or less (For Y2,Y3 and Y4)
21.6 to 26.4 V DC
6 mA/point (For Y0 and Y1)
3 mA/point (For Y2, Y3, and Y4)
Zener diode
LCD display (I/O monitor mode)
Description
Note1)
Note2)