Panasonic AFPE224300 User Manual page 220

Fp-e series panel mounted controller
Hide thumbs Also See for AFPE224300:
Table of Contents

Advertisement

Error
Name
code
System
watching
E43
dog timer
error
Slave
staiton
connecting
E44
time error
for
MEWNET-F
system
Operation
E45
error
11-122
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Opera-
tion
Description and steps to take
status
Scan time required for program
execution exceeds the setting of the
system watching dog timer.
⇒ Check the program and modify it so
Selec-
that the program can execute a scan
within the specified time.
table
Selection of operation status using
system register24:
-to continue operation,set 1
-to stop operation,set 0
The time required for slave station
connection exceeds the setting of the
system register 35.
Selec-
Selection of operation status using
table
system register25:
-to continue operation,set 1
-to stop operation,set 0
Operation became impossible when a
high-level instruction was executed.
Selection of operation status using
system register26:
-to continue operation,set K1
-to stop operation,set K0
In the FP2,FP2SH,and FP10SH,Check
the contents of special data registers
DT90017,DT90018 to find the instruction
Selec-
address where the operation error
table
occurred. Then correct the program.
In the FP3,Check the contents of special
data registers DT9017,and DT9018 to
find the instruction address where the
operation error occurred.Then correct
the program.
Verification is possible in FPWIN GR/Pro
at"I/O error" in the status display
function.
A A
A A A A
A A A A A A A A A
A:Available