I/O Allocation - Panasonic AFPE224300 User Manual

Fp-e series panel mounted controller
Hide thumbs Also See for AFPE224300:
Table of Contents

Advertisement

9.2 I/O Allocation

- I/O Allocation of FP-e control unit
Contact
Description
X0
External input
X1
External input
X2
External input
X3
External input
X4
External input
X5
External input
X6
External input
X7
External input
X8
Not used.
XF
X10
CH.0 Temperature data (WX1)
X1F
X20
CH.1 Temperature data (WX2)
X2F
X30
Front switch input "0" switch
X31
Front switch input "1" switch
X32
Front switch input "2" switch
X33
Front switch input "3" switch
X34
Front switch input "4" switch
X35
Front switch input "5" switch
X36
Front switch input "1/2/SET" switch
X37
Front switch input "MODE" switch
X38
Front switch input "0" switch
X39
Front switch input "1" switch
X3A
Front switch input "2" switch
X3B
Front switch input "3" switch
X3C
Front switch input "4" switch
X3D
Front switch input "5" switch
X3E
Front switch input "1/2/SET" switch
X3F
Front switch input "MODE" switch
X40
Data setting error (Out of the specified 16-bit)
X41
Determination of N mode 1
X42
Determination of N mode 2
X43
Determination of R mode 1
X44
Determination of R mode 2
X45
Not used.
X46
Not used.
X47
Not used.
X48
Not used.
X49
N mode 1
X4A
N mode 2
X4B
R mode 1
X4C
R mode 2
X4D
Not used.
X4E
CH. 0 Temperature conversion completion flag
X4F
CH. 1 Temperature conversion completion flag
Note 1) To cancel the data change, press the operation switch "5" for 1 second, or switch the mode using the
RUN/PROG. switch.
The data change can also be cancelled by turning Y38 ON. (Ver.1.1 or higher)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
st
screen data
nd
screen data
st
screen data
nd
screen data
st
screen data is being changed.
nd
screen data is being changed.
st
screen data is being changed.
nd
screen data is being changed.
Note
X0 to X5: Used for thermocouple input type.
X6, X7: Not used. (Thermocouple input type)
Used only for thermocouple input type.
Used only for thermocouple input type.
Available when the mode is set to S or I mode
(Not available when the mode is set to "LOCK.")
Note: X30 to X3F do not turn ON in the 1
ning after the mode is set to RUN.
Available in all modes
(Available even when the mode is set to "LOCK.")
Note: X30 to X3F do not turn ON in the 1
after the mode is set to RUN.
When the data change starts: 0
When the data is determined: 1
When the data is being changed: 1
Date is determined or cancelled: 0
st
scan-
st
scan
Note 1)
9-9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afpe224305Afpe224322Afpe224302Afpe214325

Table of Contents