Output Specifications Of The 64-Point Digital Output Unit (Sink Type) - Panasonic GM1 Series Reference Manual

Motion controller
Hide thumbs Also See for GM1 Series:
Table of Contents

Advertisement

Limitations on the number of simultaneous input ON points of the 64-point
digital input unit

11.3.2 Output Specifications of the 64-point Digital Output Unit (Sink Type)

Output specifications (sink type)
Item
Insulation method
Output type
Rated load voltage
Allowable load voltage range
Max. load current
Common restrictions
Max. inrush current
OFF state leakage current
ON state max. voltage drop
Response time
External power
supply
Surge absorber
Short-circuit protection
Input points per common
Operating mode indicator
External connection method
WUME-GM1H-02
Specifications
Optical coupler
Open collector
5 to 24 V DC
4.75 to 26.4 V DC
0.3 A (20.4 to 26.4 V DC), 30 mA (4.75 V DC)
3.2 A/common
0.6 A
1 µA or less
0.5 V or less
OFF→ON
0.1 ms or less (Load current: 2 mA or more)
ON→OFF
0.3 ms or less (Load current: 2 mA or more)
Voltage
4.75 to 26.4 V DC
Current
70 mA/common (at 24 V)
Zener diode
None
32 points/1 common
32-point LED display (Lit when ON, selection using the display selector
switch)
Connector connection (Compliant with the MIL standard, 40P, two pieces
used)
11.3 Specifications of Expansion Units