are used. The same type of module (A1A2_BS) is used for different busbars, that
is, for both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
S1S2OPTR
No bus-section coupler connection between bus-sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay that contains the above information.
For a bus-coupler bay in section 1, these conditions are valid:
BBTR_OP (sect.1)
DCOPTR (A1A2)
DCOPTR (B1B2)
BBTR_OP (sect.2)
VP_BBTR (sect.1)
VPDCTR (A1A2)
VPDCTR (B1B2)
VP_BBTR (sect.2)
EXDU_12 (sect.1)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_12 (sect.2)
IEC04000483 V1 EN-US
Figure 329:
Signals to a bus-coupler bay in section 1 from any bays in each
section
For a bus-coupler bay in section 2, the same conditions as above are valid by
changing section 1 to section 2 and vice versa.

Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the signals
BC_12 from the busbar coupler of the other busbar section must be transmitted to
the own busbar coupler if both disconnectors are closed.
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_BC
IEC04000484 V1 EN-US
Figure 330:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
BBTR_OP
&
>1
VP_BBTR
&
EXDU_12
&
en04000483.vsd
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
Line distance protection REL670 2.2 IEC
1MRK 506 369-UEN B
M13553-58 v5
A2
B2
C
en04000484.vsd