ABB REL670 2.2 IEC Applications Manual page 685

Relion 670 series line distance protection version 2.2 iec
Table of Contents

Advertisement

1MRK 506 369-UEN B
Line distance protection REL670 2.2 IEC
Application manual
Section 1
(WA1)A1
(WA2)B1
DB_BUS DB_BUS
IEC04000498 V1 EN-US
Figure 344:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of all disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of all disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from double-breaker bay (DB) that contains the above
information.
These signals from each double-breaker bay (DB_BUS) are needed:
Signal
QB1OPTR
QB1 is open.
QB2OPTR
QB2 is open.
VPQB1TR
The switch status of QB1 is valid.
VPQB2TR
The switch status of QB2 is valid.
EXDU_DB
No transmission error from the bay that contains the above information.
The logic is identical to the double busbar configuration "Signals in single breaker
arrangement".
For a bus-section disconnector, these conditions from the A1 busbar section are
valid:
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
DB_BUS DB_BUS
Section 15
Control
A2
B2
en04000498.vsd
679