1MRK 506 369-UEN B
Line distance protection REL670 2.2 IEC
Application manual
The connections are similar in all SESRSYN functions, apart from the breaker
position indications. The physical analog connections of voltages and the
connection to the IED and SESRSYN function blocks must be carefully checked in
PCM600. In all SESRSYN functions the connections and configurations must
abide by the following rules: Normally apparatus position is connected with
contacts showing both open (b-type) and closed positions (a-type).
WA1_QA1:
•
B1QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging
disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting CBConfig = 1 1/2 bus CB
TIE_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging
disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging
disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting CBConfig = Tie CB
WA2_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging
disconnectors
•
B2QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting CBConfig = 1 1/2 bus alt. CB
Section 15
Control
607