ABB REL670 2.2 IEC Applications Manual page 557

Relion 670 series line distance protection version 2.2 iec
Table of Contents

Advertisement

1MRK 506 369-UEN B
Line distance protection REL670 2.2 IEC
Application manual
Table 42:
Settings
U/f op (%)
Timer
105
t1
112
t2
119
t3
126
t4
133
t5
140
t6
Information on the cooling time constant T
transformer manufacturer.
V/Hz
%
150
140
130
120
110
100
0.05
0.1
0.2
0.5
t6
t5
t4
IEC01000377 V1 EN-US
Figure 290:
Example on overexcitation capability curve and V/Hz protection
settings for power transformer
Time set (s)
7200 (max)
600
60
20
8
4
should be retrieved from the power
cool
transformer capability curve
relay operate characteristic
1
2
5
10
t3
t2
Section 10
Voltage protection
Continous
20
50
100
200
(minutes)
t1
en01000377.vsd
Time
551