Signals In 1 1/2 Breaker Arrangement - ABB REL670 2.2 IEC Applications Manual

Relion 670 series line distance protection version 2.2 iec
Table of Contents

Advertisement

1MRK 506 369-UEN B
15.4.6.4
Line distance protection REL670 2.2 IEC
Application manual
QB2OPTR (bay 1/sect.B1)
. . .
. . .
. . .
QB2OPTR (bay n/sect.B1)
VPQB2TR (bay 1/sect.B1)
. . .
. . .
. . .
VPQB2TR (bay n/sect.B1)
EXDU_DB (bay 1/sect.B1)
. . .
. . .
. . .
EXDU_DB (bay n/sect.B1)
IEC04000501 V1 EN-US
Figure 347:
Signals from double-breaker bays in section B1 to a bus-section
disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are
valid:
QB2OPTR (bay 1/sect.B2)
. . .
. . .
. . .
QB2OPTR (bay n/sect.B2)
VPQB2TR (bay 1/sect.B2)
. . .
. . .
. . .
VPQB2TR (bay n/sect.B2)
EXDU_DB (bay 1/sect.B2)
. . .
. . .
. . .
EXDU_DB (bay n/sect.B2)
IEC04000502 V1 EN-US
Figure 348:
Signals from double-breaker bays in section B2 to a bus-section
disconnector

Signals in 1 1/2 breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbar
disconnector bay no other disconnector connected to the bus-section must be made
by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,
corresponding signals from busbar B are used.
Section 15
S1DC_OP
&
VPS1_DC
&
EXDU_BB
&
en04000501.vsd
S2DC_OP
&
VPS2_DC
&
EXDU_BB
&
en04000502.vsd
Control
M13542-127 v5
681