Light scene extension unit with memory function
Pos: 22.27 /KNX/Applikationsbeschreibungen/Applikationen - App/Lichtszenennebenstelle_mit_Speicherfunktion/App. - Lichtszenennebenstelle mit Speicherfunktion - DIN-A4 @ 9\mod_1269435757171_15.doc @ 52778 @
Via the application "Light scene extension unit with memory function", a predefined light scene number is called up when the
rocker is actuated.
The application "Light scene extension unit with memory function" makes a separate set of parameters and communication
objects available in each case for the right or left side of the rocker.
The application facilitates calling up a light scene via a rocker side while the other rocker side can be assigned an additional
"button orientated" function.
The user has the option to trigger a light scene memory command with a long button contact.
Light scene extension unit objects with memory function
No.
Function
0
Switching
Pos: 22.28 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Stufenschalter, Wippe Gesamt @ 9\mod_1269437200187_15.doc @ 52793 @ 22
Step switch, rocker total
Pos: 22.29 /KNX/Applikationsbeschreibungen/Applikationen - App/Stufenschalter_Wippe_gesamt/App. - Stufenschalter, Wippe Gesamt - DIN-A4 @ 9\mod_1269436921171_15.doc @ 52788 @
The application "Step switch, rocker total" facilitates step-type switching. This means that the user can trigger different
switching processes with each new operation of the left or right side of the rocker.
Example:
First operation (right rocker side) switches lamp 1 on.
Second operation (right rocker side) switches lamp 1 off and lamp 2 on.
Third operation (right rocker side) switches lamp 2 off and lamp 3 on.
Fourth operation (left rocker side) switches lamp 3 off and lamp 2 on.
Fifth operation (left rocker side) switches lamp 2 off and lamp 1 on.
etc.
The application differentiates between whether the left or right side of the rocker was operated. Depending on the setting,
one lower or one higher step can be switched to.
Up to five switching steps can be activated.
Step switch objects, rocker total
No.
Object name
0
Switching step 1
1
Switching step 2
2
Switching step 3
3
Switching step 4
4
Switching step 5
Pos: 22.30 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @ 2
Object name
Data type
1 Byte EIS1 / DPT 1.001
Data type
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
KNX Technical Reference Manual | 0073-1-7388 | 25
Flags
C, W, T, U
Flags
C, W, T
C, W, T
C, W, T
C, W, T
C, W, T