KNX Technical Reference Manual
Busch-priOn
Pos: 22.36 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Kurz-Lang-Bedienung, Wippe Links / Rechts @ 9\mod_1269440952703_15.doc @ 52823 @ 22

Short/long operation, rocker left/right

Pos: 22.37 /KNX/Applikationsbeschreibungen/Applikationen - App/Kurz_lang_Bedienung_Wippe_links_rechts/App. - Kurz-Lang-Bedienung, Wippe Links / Rechts - DIN-A4 @ 9\mod_1269440785765_15.doc @ 52818 @ 2
Via the application "Short/long operation, rocker left/right", different values can be sent out with a short and/or long actuation
of the rocker switch.
The "Short/long operation, rocker left/right" application does not differentiate between whether the rocker is actuated on the
left or right side. In each case, the application makes a separate set of parameters and communication objects available for
the right and left side of the rocker.
The application facilitates making two separate functions available on one side of the rocker that can be called up via a short
or long button contact and assigning the other side of the rocker switch with an additional "button-orientated" function.
Short/long operation objects, rocker left/right
No.
Object name
0
Adjusting(1 Bit)
0
Adjusting(1 Byte)
1
Moving (1 Bit)
1
Moving (1 Byte)
Pos: 22.38 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/P - R/RTR-Betriebsart einstellen @ 9\mod_1269441295921_15.doc @ 52833 @ 22
Setting RTC operation mode
Pos: 22.39 /KNX/Applikationsbeschreibungen/Applikationen - App/RTR-Betriebsart/App. - RTR-Betriebsart einstellen - DIN-A4 @ 9\mod_1269441072468_15.doc @ 52828 @
With the "Setting the RTC operation mode" application, an operation mode switchover for connected room temperature
controllers can be carried out via an actuation of a rocker side.
Depending on the setting of the "Object type for output" parameter, the application offers either three 1-bit communication
objects "Operation mode comfort", "Operation mode night", and "Operation mode frost" or a 1-byte communication object
"Operation mode".
The selection "1-bit" is used for the control of room temperature controllers that have 1-bit communication objects for
operation mode switchover. The "1-byte" selection is used for the control of room temperature controllers that have a 1-byte
communication object for operation mode switchover to KNX. In this case, the values mean
0 = Auto
1 = Comfort
2 = Standby
3 = Night
4 = Frost / Heat protection
The function can be temporarily blocked via a 1-bit "Enable" communication object.
Setting RTC operation mode objects
No.
Object name
0
Enable
1
Operation mode Comfort(1 Bit)
2
Operation mode Night(1 Bit)
3
Operation mode Frost(1 Bit)
4
Operation mode (1 Byte)
Pos: 22.40 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @ 22
28 | 0073-1-7388 | KNX Technical Reference Manual
®
Data type
1 Bit EIS7 / DPT 1.007
1 Byte EIS6 / DPT 5.001
1 Bit EIS7 / DPT 1.008
1 Byte EIS6 / DPT 5.001
Data type
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Byte / DPT 20.102
Flags
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
Flags
C, W, U
C, T
C, T
C, T
C, T