ABB Busch-priOn Series Technical Reference Manual page 41

Knx technical reference manual
Table of Contents

Advertisement

Pos: 22.88 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Treppenhauslicht @ 9\mod_1269509802172_15.doc @ 53113 @ 22
Staircase lighting
Pos: 22.89 /KNX/Applikationsbeschreibungen/Applikationen - App/Treppenhauslicht/App. - Treppenhauslicht - DIN-A4 @ 9\mod_1269509557128_15.doc @ 53098 @
With the "Staircase lighting" application, switching telegrams or value telegrams can be provided with a light-on time.
Depending on the parameterisation, the application shows different communication objects:
- a 1-bit object for input and output
If an ON telegram is received via the "Input/Output" object, the light-on time is started immediately. This can be a light-on
time of 00:10 min to 88:45 min, which is adjustable in 0.1 s steps. After expiration of the light-on time, the "Input/Output"
object sends an OFF telegram.
- two 1-bit objects for input and output
- and two 1-byte objects for input and output
If a telegram is received via the "Input" object, the light-on time is started immediately and a telegram with the same value of
the telegram received on the input is sent out on the "Output" object. This can be a light-on time of 00:10 min to 88:45 min,
which is adjustable in 0.1 s steps. After expiration of the light-on time, the "Output" object sends out an OFF telegram (1-bit)
or a telegram with the value "0" (1-byte).
Via two additional communication objects, it is possible to specify the light-on time and the switch-off prewarning time. The
2-byte values received are written to the memory of the device and are retained even after a bus power failure and
subsequent return of voltage.
Staircase lighting objects
No.
Object name
0
Input (1 Bit)
0
Input (1 Byte)
0
Input_Output (1 Bit)
1
Light-on time (2 Byte)
2
Switch-off pre-warning
3
Output (1 Bit)
3
Output (1 Byte)
Pos: 22.90 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @
Data type
1 Bit EIS1 / DPT 1.001
1 Bit EIS14 / DPT 5.010
1 Bit EIS1 / DPT 1.001
2 Byte EIS10 / DPT 7.001
2 Byte EIS10 / DPT 7.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS14 / DPT 5.010
KNX Technical Reference Manual | 0073-1-7388 | 41
Flags
C, W
C, W
C, W, T
C, R, W
C, R, W
C, T
C, T

Hide quick links: