Busch-priOn
Pos: 22.70 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Jalousieaktor @ 10\mod_1269514191049_15.doc @ 53234 @ 22
Shutting actuator
Pos: 22.71 /KNX/Applikationsbeschreibungen/Applikationen - App/Jalousieaktor/App. - Jalousieaktor - DIN-A4 @ 10\mod_1269513864598_15.doc @ 53229 @
With the "Shutting actuator" application the shutting actuator is activated (Flush-type switch actuator 2-gang).
It has two 1-bit communication objects "Move" and "Adjust". In addition, the Venetian blind can be moved to a defined
position via the 1-byte communication objects "Position" and "Slats position".
The behaviour can be adjusted so that no undefined state arises during a bus voltage recovery.
There is also the option of additionally activating a 1-bit communication object "Status response". The shutting actuator can
send out its current state over this.
Shutting actuator objects
No.
Object name
0
Move
1
Adjust
1
Stop
2
Position
3
Slats position
4
Wind alarm
5
Rain alarm
6
Frost alarm
7
Move status
8
Position state
9
Slats position status
Pos: 22.72 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Schaltaktorapplikation @ 10\mod_1269514683702_15.doc @ 53245 @ 222

Switch actuator application

Pos: 22.73 /KNX/Applikationsbeschreibungen/Applikationen - App/Schaltaktorapplikation/App. - Schaltaktorapplikation - DIN-A4 @ 10\mod_1269514450016_15.doc @ 53240 @
The flush-type switch actuator is activated with the "Switch actuator application" application.
For this the application has a 1-bit communication object "Switch object". Depending on the setting of the "Relay
characteristics" parameter, the relay contact is opened or closed after receipt of an ON or OFF telegram.
The behaviour can be adjusted so that no undefined state arises after a bus voltage failure and subsequent return of voltage.
There is also the option of activating an additional 1-bit communication object "Status response". The switching actuator can
send out its current state over this. Whether an ON or an OFF telegram is triggered during a closed or an opened relay
contact depends on the setting of the "Relay characteristics" and "Invert status response" parameters.
Switch actuator application objects
No.
Object name
0
Switch object
1
Status response signal
Pos: 22.74 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @
36 | 0073-1-7388 | KNX Technical Reference Manual
®
Data type
1 Bit EIS7 / DPT 1.008
1 Bit EIS7 / DPT 1.007
1 Bit / DPT 1.017
1 Byte EIS5 / DPT 5.001
1 Byte EIS5 / DPT 5.001
1 Bit / DPT 1.005
1 Bit / DPT 1.005
1 Bit / DPT 1.005
1 Bit EIS7 / DPT 1.008
1 Byte EIS5 / DPT 5.001
1 Byte EIS5 / DPT 5.001
Data type
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
Flags
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, R, T
C, R, T
C, R, T
Flags
C, W
C, T