The "Preset" application makes an input and output communication object available. At the receipt of a switching telegram
on the 1-bit input object, a telegram is immediately sent out on the 1-byte output object. A preset percent value or,
alternatively, a light scene number can be sent out.
Preset objects
No.
Object name
0
Input (1 Bit)
0
Output (1 Byte 0..100 %)
0
Output (1-byte light scene number)
Pos: 22.98 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Telegramm zyklisch @ 10\mod_1269511714991_15.doc @ 53163 @ 22
Cyclic telegram
Pos: 22.99 /KNX/Applikationsbeschreibungen/Applikationen - App/Telegramm zyklisch/App. - Telegramm zyklisch - DIN-A4 @ 10\mod_1269511411745_15.doc @ 53158 @
Via the "Cyclic telegram" application and after receipt of a telegram on the "Input" object, a telegram with the same volume is
cyclically sent out on the "Cyclic output" object.
The object types for "Input" and "Output" can be collectively parameterised for the different applications.
The times for cyclic sending on the "Output" object are adjustable.
Via an additional "Enable" object, there is the option of temporarily blocking the function.
Cyclic telegram objects
No.
Object name
0
Input (1-bit switching)
0
Input (1-bit alarm)
0
Input (1 Byte 0..100 %)
0
Input (1 Byte 0..255)
0
Input (2 Byte Float)
0
Input (2 Byte Signed)
0
Input (2 Byte Unsigned)
0
Input (2-byte temperature)
0
Input (4 Byte Float)
0
Input (4 Byte Signed)
0
Input (4 Byte Unsigned)
1
Output (1-bit switching)
1
Output (1-bit alarm)
1
Output (1 Byte 0..100 %)
1
Output (1 Byte 0..255)
1
Output (2 Byte Float)
1
Output (2 Byte Signed)
1
Output (2 Byte Unsigned)
1
Output (2-byte temperature)
1
Output (4 Byte Float)
1
Output (4 Byte Signed)
1
Output (4 Byte Unsigned)
2
Enable
Pos: 22.100 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc @ 52149 @
Data type
1 Bit EIS1 / DPT 1.001
1 Byte EIS6 / DPT 5.001
1 Byte / DPT 18.001
Data type
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Byte EIS6 / DPT 5.001
1 Byte EIS14 / DPT 5.010
2 Byte EIS5 / DPT 9.xxx
2 Byte EIS10 / DPT 8.001
2 Byte EIS10 / DPT 7.001
2 Byte EIS5 / DPT 9.001
4 Byte EIS9 / DPT 14.xxx
4 Byte EIS11 / DPT 13.001
4 Byte EIS11 / DPT 12.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS1 / DPT 1.001
1 Byte EIS6 / DPT 5.001
1 Byte EIS14 / DPT 5.010
2 Byte EIS5 / DPT 9.xxx
2 Byte EIS10 / DPT 8.001
2 Byte EIS10 / DPT 7.001
2 Byte EIS5 / DPT 9.001
4 Byte EIS9 / DPT 14.xxx
4 Byte EIS11 / DPT 13.001
4 Byte EIS11 / DPT 12.001
1 Bit EIS1 / DPT 1.001
KNX Technical Reference Manual | 0073-1-7388 | 43