LBS and Internal Options
NOTE
These items must be enabled by service to be functional.
Load Bus Synch —Enable/Disable (default: disable)
Figure 16 Load Bus Sync (not available on the display screen)
Input Contact Isolator Board
• Assignment—Custom, Pre-assigned (default: "Input Contact" XY)
• Delay, sec—0 to 99.9 (default: 0)
• Message—Custom: 0-19 characters

Figure 17 Input Contact Isolator Board screen

Page 26
Operation and Maintenance Manual
250-300-400-800kVA