Emerson Liebert NXL series Operation And Maintenance Manual page 81

250 to 800kva, 50/60hz, three phase single-module and 1+n
Table of Contents

Advertisement

Liebert NXL UPS
Event Message
Event Definition
Inlet Ovtemp
The air flowing into the UPS is too
warm.
This alarm is self-clearing. When the
condition is no longer present, the alarm
and any control activity tied to the
alarm reverts to normal.
Excess Auto
The UPS has re-transferred too many
Rexfers
times and is now locked on bypass.
The UPS attempts to perform an
automatic transfer back to Inverter, if
the reason for the transfer to bypass is
determined by the controls to be
automatically recoverable; for example,
a temporary overload.
The number of times the UPS attempts
to recover from an automatic transfer to
bypass is limited.
When the number of transfers exceeds
the number allowable (default is 5
transfers per hour), the UPS remains on
bypass, and display this message.
An example of a condition that could
cause this alarm is cycling load to the
UPS where the peak load exceeds the
overload settings. The UPS transfers on
the overload, re-transfers to Inverter,
then the overload returns. Once this
occurs 5 times within one hour, the user
must manually transfer the UPS back
online.
Excess
When the controls detect a high
Paralleling
amplitude, short duration overload
condition on the output, the static
switch is turned on momentarily in
parallel with the Inverter to attempt to
clear the condition.
If the fault clears, the controls turn off
the static switch and the load remains
on Inverter. This fault condition
indicates the UPS pulse paralleled too
many times and is now locked on bypass
(auto re-transfers to Inverter are
inhibited).
Liebert NXL alarm and status messages (continued)
Page 81
Operation and Maintenance Manual
250-300-400-800kVA
Recommended Action
Press "SILENCE" to silence the audible
alarm.
Check the Inlet Air Temperature on the
One-Line Display and verify the reading
is accurate, i.e. is the room temperature
warmer than normal?
If the room temperature is warmer than
normal, investigate and resolve the issue.
If the room temperature is normal, and
the Inlet Air Temp reading on the One-
Line Display is higher than normal,
contact your factory-authorized service
provider.
Press "SILENCE" to silence the audible
alarm.
Press "RESET" to clear any active faults
or alarms.
Provided there are no alarms or faults
still present that could prevent a transfer,
press "Transfer," "UPS," to transfer back
to Inverter.
If the transfer is successful, press
"RESET" to clear the alarm. Otherwise,
contact your factory-authorized service
provider.
Press "SILENCE" to silence the audible
alarm.
Check the Module Output Meter and
verify the output currents are normal, the
kVA/kW percentages are less than 100%,
and the Rexfer Timeout is 00:00.
Verify the Inverter box on the One-Line
Display is green.
Investigate any other active alarms or
faults before attempting to clear this
fault.
Press "RESET" to clear the fault.
If the Event Window is clear, press
"Transfer," "UPS" to transfer the load
back to Inverter.
If the "UPS" button is grayed out, or
pressing the "UPS" button does not
transfer the unit back to Inverter, or if
the UPS immediately transfers back to
bypass, contact your factory-authorized
service provider.

Advertisement

Table of Contents
loading

Table of Contents