Figure 15 Typical Event Management Parameters - Emerson Liebert NXL series Operation And Maintenance Manual

250 to 800kva, 50/60hz, three phase single-module and 1+n
Table of Contents

Advertisement

Liebert NXL UPS
2.2.6.5
2.2.6.5
2.2.6.5
2.2.6.5
Event Management
This menu item permits changing how the Liebert NXL handles Alarms, Faults and Status
information. Each event can be configured for the following:
• Latch (yes/no)—Event stays active in the event window, even if the fault condition has
been cleared, until user acknowledges it by pressing the "Reset" button.
• Audible (yes/no)—Will set Audible alarm when event occurs
• Event log (yes/no)—Will display event in Event log when it occurs
NOTE
You must press "Save" for changes to take effect.
See Table 6 for a list of alarms, fault and status messages.

Figure 15 Typical Event Management Parameters

Page 25
Operation and Maintenance Manual