Liebert NXL UPS
6)
Start rectifier: After bypass started, then enter the process of starting
rectifier on the LCD, as shown in figure above (Rectifier section will be green).
Press Ok button, then rectifier start as shown in figure below.
Page 51
Operation and Maintenance Manual
Figure 40 Rectifier ON command
Figure 41 Load on Bypass, UPS available
250-300-400-800kVA