Emerson Liebert NXL series Operation And Maintenance Manual page 67

250 to 800kva, 50/60hz, three phase single-module and 1+n
Table of Contents

Advertisement

Liebert NXL UPS
Liebert NXL Model Size
System Parameters
UPS Efficiency AC-AC 100%
Load (w/o any power option)
UPS Efficiency AC-AC 40÷80%
Load (w/o any power option)
Physical Parameters&Standards
Width 6 Pulse
Width 12 Pulse
Depth
Height
Weight 6 Pulse (approx.)
Weight 12 Pulse (approx.)
Colour
Front Door Opening (for
serviceability)
Degree of Protection for UPS
Enclosure
Acoustical Noise
Standards & Conformities
Disclosures with Regard to Embedded Software Licensed from TrollTech, Inc.,
("Sublicensed Software")
1. Limits on Use, Distribution and Derivative Works: User is not given any rights to modify or
create derivative works based on Sublicensed Software, or reproduce Sublicensed Software, or
distribute any copies of Sublicensed Software, or disclose any Sublicensed Software to any third
party, or decompile, disassemble or otherwise reverse engineer Sublicensed Software, or use
any information learned therefrom. User acknowledges that TrollTech, Inc., and its licensors
own the copyrights and other intellectual property in and to the Sublicensed Software.
2. Responsibility of User: The Sublicensed Software is not designed, intended or licensed for use
in or with systems, devices or products intended for surgical implant into the body or other
applications intended to support or sustain life or for any aviation or nuclear reactor. It is
User's responsibility to ascertain the suitability of Sublicensed Software for any situation or
application.
Page 67
Operation and Maintenance Manual
Units
250
%
%
mm
1430
mm
2045
mm
mm
kg
1700
kg
2420
-
dBA
EN 62040-1-1 (2003), EN 62040-2 (2006), EN 62040-3 (2001)
The above mentioned product standards incorporate relevant compliance clauses with
generic IEC and EN standards for safety (60950), electromagnetic emission and
Electrical Specifications - 250-300-400kVA UPS (continued)
300
≥ 93.5 (depends on rating & operating conditions)
≥ 92.5 (depends on rating & operating conditions)
1600
2215
850
1950
1880
2710
RAL 7021
More than 180°
IP 20 even with front door in opened condition
67
CE MARK
immunity (61000 series) and construction (60529)
250-300-400-800kVA
400
1600
2385
990
2370
3490
69