Startup Menu; Shutdown Menu; Figure 20 Shutdown Menu - Emerson Liebert NXL series Operation And Maintenance Manual

250 to 800kva, 50/60hz, three phase single-module and 1+n
Table of Contents

Advertisement

Liebert NXL UPS
2.2.8

Startup Menu

This menu is used to start the UPS and individual devices.
2.2.8.1
2.2.8.1
2.2.8.1
2.2.8.1
Manual start-up
Manual—This will begin the UPS startup. See 2.5 - Manual Procedures for details.
2.2.8.2
2.2.8.2
2.2.8.2
2.2.8.2
Device control
Devices
• Close Trap—This will start the Input filter, if installed
• Close BCB—The Close command will Enable the breaker UVR. The BCB must be
closed manually. If no BCB is selected, do not display this setting.
2.2.9

Shutdown Menu

This menu permits shutting down the UPS and individual devices.
2.2.9.1
2.2.9.1
2.2.9.1
2.2.9.1
Open Input Trap filter
Open Trap—Opens the input trap filter
2.2.9.2
2.2.9.2
2.2.9.2
2.2.9.2
Open BCB
Open BCB—Opens the associated BCB breaker
Page 29
Operation and Maintenance Manual

Figure 20 Shutdown menu

250-300-400-800kVA