Chapter 2
Alarm Troubleshooting
For information about provisioning the ML-100T-8 Ethernet cards from the Cisco IOS interface, refer to
Note
the Cisco ONS 15310-CL and Cisco ONS 15310-MA Ethernet Card Software Feature and Configuration
Guide.
Clear the ERROR-CONFIG Alarm
If the ML-100T-8 Ethernet configuration is different from the actual installation, create the correct
Step 1
startup configuration based upon the installation.
Consult the ML-100T-8 POS provisioning parameters for the card and POS ports in the
Cisco ONS 15310-CL and Cisco ONS 15310-MA Ethernet Card Software Feature and Configuration
Guide.
Step 2
Upload the configuration file to the controller card (ONS 15310-MA SDH) by completing the following
steps:
a.
b.
c.
Step 3
Complete the
Avoid soft-resetting multiple ONS 15310-MA SDH cards at one time; doing so might cause an
Caution
unexpected traffic hit.
If the alarm does not clear or if your configuration file was correct according to the installed card, start
Step 4
a Cisco IOS CLI for the card by completing the following steps:
a.
b.
Follow the card provisioning instructions in the Cisco ONS 15310-CL and Cisco ONS 15310-MA
Ethernet Card Software Feature and Configuration Guide to correct the errored configuration file line.
Execute the following CLI command:
Step 5
copy run start
The command copies the new card configuration into the database and clears the alarm.
If the alarm does not clear, log into the Technical Support Website at
Step 6
http://www.cisco.com/cisco/web/support/index.html for more information or call Cisco TAC
(1-800-553-2447).
78-18663-01
The user stored the configuration for one type of ML-100T-8 Ethernet card in the database and then
installed another type in its slot.
The configuration file contained a syntax error.
In node view, right-click the ML-100T-8 Ethernet card graphic.
Choose IOS Startup Config from the shortcut menu.
Click Local > TCC and navigate to the file location in the Open dialog box.
"Soft- or Hard-Reset an Ethernet or Electrical Card in CTC" procedure on page
Right-click the ML-100T-8 Ethernet card graphic in node view.
Choose Open IOS Connection from the shortcut menu.
"Open IOS Connection" is not available unless the ML-100T-8 Ethernet card is physically
Note
installed in the shelf.
Cisco ONS 15310-MA SDH Troubleshooting Guide, Release 9.0
Alarm Procedures
2-151.
2-55