Alarm Procedures
Complete the
Step 2
the reporting card.
Avoid soft-resetting multiple ONS 15310-MA SDH cards at one time; doing so might cause an
Caution
unexpected traffic hit.
For the LED behavior, see the
If the CTC reset does not clear the alarm, complete the
Step 3
procedure on page 2-153
Always use the supplied electrostatic discharge wristband when working with a powered
Caution
ONS 15310-MA SDH.
Step 4
If the physical reseat of the card fails to clear the alarm, complete the
procedure on page 2-153
Note
If the alarm does not clear, log into the Technical Support Website at
Step 5
http://www.cisco.com/cisco/web/support/index.html for more information or call Cisco TAC
(1-800-553-2447) in order to report a Service-Affecting (SA) problem.
2.7.56 EQPT-MISS
The Replaceable Equipment or Unit Missing alarm is reported against the fan tray within the
ONS 15310-MA SDH. It indicates that the fan is not operational, or that the ONS 15310-MA SDH fan
tray is not present. For the ONS 15310-MA SDH, complete the fan tray replacement procedure located
in the Cisco ONS15310-MA SDH Procedure Guide.
If the alarm does not clear, log into the Technical Support Website at
http://www.cisco.com/cisco/web/support/index.html for more information or call Cisco TAC
(1-800-553-2447) in order to report a Service-Affecting (SA) problem.
2.7.57 ERROR-CONFIG
The Error in Startup Configuration alarm applies to the ML-100T-8 Ethernet cards. These cards process
startup configuration files line by line. If one or more lines cannot be executed, the error causes the
ERROR-CONFIG alarm. ERROR-CONFIG is not caused by hardware failure.
The typical reasons for an errored startup file are:
Cisco ONS 15310-MA SDH Troubleshooting Guide, Release 9.0
2-54
"Soft- or Hard-Reset an Ethernet or Electrical Card in CTC" procedure on page 2-151
for the reporting card.
for the reporting card.
When you replace a card with the identical type of card, you do not need to make any changes
to the database.
Default Severity: Critical (CR), Service-Affecting (SA)
SDH Logical Object: FAN
Default Severity: Minor (MN), Non-Service-Affecting (NSA)
SDH Logical Object: EQPT
"2.8.2 Typical Card LED Activity During Reset" section on page
"Remove and Reinsert (Reseat) a Card"
Chapter 2
Alarm Troubleshooting
"Physically Replace a Card"
78-18663-01
for
2-146.