7 TECHNICAL SPECIFICATION

GENERAL DATA
Output rated power [W]
Output power factor
Topology
Parallel configuration
Inbuilt batteries
INPUT
Nominal input voltage
Input voltage tolerance
Input current THD
Frequency range
Power factor
OUTPUT
Rated output voltage
Voltage tolerance
(referred to 230V)
Voltage distortion
Overload capability
Nominal frequency
Crest Factor
TRANFER TIME
Battery ßà inverter
Inverter to Eco-mode
Eco-mode to inverter
EFFICIENCY
AC-AC
In eco-mode
ENVIRONMENT
Protection rating
Storage temperature
Operating temperature
Relative humidity
Altitude
(above sea level)
BATTERIES
Type
Number of batteries
Charging current
Recharge time
COMMUNICATIONS
User interface
Communication cards
(option)
STANDARDS
Safety
EMC
Performance
Manufacturing
WEIGHT, DIMENSIONS
Weight
Dimensions
WxHxD
*Technical specifications are subject to change without notice.
6000 VA
5400 W
0.9
True online double conversion
Up to 2 units
yes
208/220/230/240 V
AC
110-276 V
(depends on load level)
AC
<5% with full resistive load
45-55 Hz / 54-66 Hz
≥0.99
208 / 220 / 230 / 240 V
AC
±1%
≤2% linear load, ≤5% non-linear load
2mins.: 102%-130% load / 30s.: 130%-150% load / 100ms.: >150% load (Inverter)
10s:. 102-130% load / 100ms.: >130% load (battery)
50 or 60 Hz ± 0.2 Hz
3:1
0 ms
1 ms
<10 ms
> 92%
> 96%
IP 20
-15 – +60°C for UPS, 0~35°C for battery
0 – 40°C
0-95% (Non-condensing)
1000m without de-rating
VRLA, vented lead-acid
No internal batteries
>8 A
External battery dependent
LCD display
SNMP, AS400 RS485 card
IEC/EN 62040-1
IEC/EN 62040-2
IEC/EN 62040-3
ISO 9001:2008, ISO 14001:2004
20.1
438x129x594
04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
Modifications reserved
10000 VA
9000 W
> 93%
>97%
28.1
438x215.5x594