Connections - ABB PowerValue 11 RT 6 kVA User Manual

Hide thumbs Also See for PowerValue 11 RT 6 kVA:
Table of Contents

Advertisement

Model
Protective Earth (PE) conductor
(Minimum cross section)
Input L, N, G (
Input fuse
Output L,N, G
External Battery Cabinet
Positive Pole(+), Negative Pole(-), Neutral Pole
(Minimum cross section)
External Battery Cabinet Fuse in Positive
Pole(+), Negative Pole (-), Neutral Pole
It is suggested to install an external isolating device against back-feed currents between mains input and UPS
as indicated in Figure 12.
WARNING!
2.4.3

Connections

To access the terminal blocks, remove the 2 screws from the terminal block cover.
Minimum cross section)
(Minimum cross section)
Figure 11: Recommended Cables and Fuses
AC Contactor:
Figure 12: External Backfeed Isolation
AFTER THE DEVICE IS INSTALLED, ADD A LABEL WITH THE
FOLLOWING WARNING ON THE EXTERNAL AC CONTACTOR: "RISK OF
BACKFEED VOLTAGE. ISOLATE THE UPS BEFORE OPERATING ON
THIS CIRCUIT AND CHECK FOR HAZARDOUS VOLTAGE"
Figure 13: PowerValue 11 RT 6 kVA Terminal block
Figure 14: PowerValue 11 RT 10 kVA Terminal block
04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
6 kVA
6mm2 (8 AWG)
6mm2 (8 AWG)
60A
6mm2 (8 AWG)
4mm2 (10 AWG)
60A
208-240V, 50A (PowerValue 11 RT 6 kVA)
208-240V, 70A (PowerValue 11 RT 10 kVA)
Modifications reserved
10 kVA
10mm2 (6 AWG)
10mm2 (6 AWG)
80A
10mm2(6AWG)
2.5mm2*2
(12 AWG*2)
80A
Page 14/37 ABB