3.4.2.4 Identification
Press
on the Identification menu to navigate through its data. The identification information includes UPS
serial number, firmware serial number and-model type.
Press
>1s to return to the last main menu.
3.4.2.5 User's Settings
Contact your local distributor for further information before using the settings. Some settings can impact on
the performance of the UPS and others can enable and disable functions within the UPS. Failures and
reduced protection can occur if the equipment is not set in an adequate way. Note that most settings should
be done only with the UPS in bypass-mode.
If the password is enabled, the user must enter the password
is used mainly to protect against modifications in the Settings menu. The possible operations are indicated in
Table 1.
Submenu item
Description
Language
Select menu language
User password*
Protects against settings modifications
Audio alarm
Enable/disable alarm sounds
Output voltage
Define local rated output voltage
Output frequency
Define local rated output frequency
Power strategy**
Define the UPS running mode to normal, ECO-mode
or Running mode
(or HE high efficiency) and converter mode
Start the UPS from the batteries (without mains
DC start
power)
Phase and neutral cables are connected in reversed
Site wiring fault alarm
positions.
Ambient temperature
Temperature is over the limit supported by the UPS
warning
Automatic battery tests
Define the frequency of the battery tests
period
After power outage, the loads restart automatically
Auto restart
when mains power is recovered.
Automatic overload
The UPS is automatically restarted if it shut downs for
restart
overload.
The automatic bypass can be disabled for countries
Auto bypass
where the power supply is very unstable. UPS runs
only online or on battery.
- When enabled, short circuit will last for 4s before
cutting off the output. If short circuit is removed during
Short circuit clearance
this time, the UPS will continue to run normally.
- When disabled, short circuit will only last for 100ms
before UPS output is cut off.
Redundancy lost (in
One of the parallel units have been disconnected from
parallel UPS systems)
the system
Bypass voltage low
When the voltage in the bypass is below this limit, the
limit
UPS changes running mode.
Bypass voltage high
When the voltage in the bypass is above this limit, the
limit
UPS changes running mode.
Bypass frequency low
When the frequency in the bypass is below this limit,
limit
the UPS changes running mode.
Bypass frequency high
When the frequency in the bypass is above this limit,
limit
the UPS changes running mode.
Figure 36: Identification menu tree
04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
Modifications reserved
USER
by pressing the buttons ,
Optional Values
Chinese/English
enabled/disabled
enabled/disabled
208/220/230/240V
autosensing/50/60Hz
normal/high efficiency/
converter
enabled/disabled
enabled/disabled
enabled/disabled
0-31 days
enabled/disabled
enabled/disabled
enabled/disabled
enabled/disabled
enable/disabled
120~215V
245~276V
1%~10%
1%~10%
and
. It
Default value
English
disabled
enabled
230V
autosensing
normal
enabled
enabled
enabled
7days
enabled
enabled
enabled
disabled
enabled
184V
264V
10%
10%