Allen-Bradley 2080-LC20-20QBB User Manual page 60

Micro820 series programmable controllers
Hide thumbs Also See for 2080-LC20-20QBB:
Table of Contents

Advertisement

Chapter 4
Wire Your Controller
50
• use Belden cable #8761 for wiring the analog channels, making sure that
the drain wire and foil shield are properly earth grounded.
• route the Belden cable separately from any AC wiring. Additional noise
immunity can be obtained by routing the cables in grounded conduit.
Grounding Your Analog Cable
Use shielded communication cable (Belden #8761). The Belden cable has two
signal wires (black and clear), one drain wire, and a foil shield. The drain wire and
foil shield must be grounded at one end of the cable.
Insulation
IMPORTANT
Do not ground the drain wire and foil shield at both ends of the cable.
Foil shield
Clear wire
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
Black wire
Drain wire