Appendix D PID Function Blocks
182
IPIDCONTROLLER Arguments
Parameter
Parameter
Type
ATWarnings
Output
OutGains
Output
ENO
Output
GAIN_PID Data Type
Parameter
Type
Description
DirectActing
BOOL
Types of acting:
TRUE = Direct acting, output moves same direction as error. That is,
the actual process value is greater than the SetPoint and the
appropriate controller action is to increase the output. For example,
Chilling.
FALSE = Reverse acting, output moves opposite direction as error.
That is, the actual process value is greater than the Setpoint and the
appropriate controller action is to decrease the output. For example,
Heating.
ProportionalGain
REAL
Proportional gain for PID (>= 0.0001).
Proportional gain for PID (P_Gain)
A higher proportional gain causes a larger change in the output
based upon the difference between the PV (measured process value)
and SV (set point value). The higher the gain, the faster the error is
decreased, but this may result in instability such as oscillations. The
lower the gain, the slower the error is decreased, but the system is
more stable and less sensitive to large errors. The P_Gain usually is
the most important gain to adjust and the first gain to adjust while
tuning.
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
Data Type Description
DINT
Warning for the AutoTune sequence. Possible value
are:
0 = No auto tune done.
1 = In auto tune mode.
2 = Auto tune done.
-1 = Error 1: Input automatically set to TRUE, no auto
tune possible.
-2 = Error 2: Auto tune error, the ATDynamSet expired.
GAIN_PID
Gains calculated from AutoTune Sequences.
Use GAIN_PID data type to define the OutGains
output.
BOOL
Enable out.
Applicable to Ladder Diagram programs.