Allen-Bradley 2080-LC20-20QBB User Manual page 145

Micro820 series programmable controllers
Hide thumbs Also See for 2080-LC20-20QBB:
Table of Contents

Advertisement

Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
PWM Typical Readings
Frequency (kHz)
%Duty Cycle
25
10%
25
20%
25
40%
25
55%
25
65%
25
85%
25
95%
50
5%
50
10%
50
20%
50
40%
50
55%
50
65%
50
85%
50
95%
100
5%
100
10%
100
20%
100
40%
100
55%
100
65%
100
85%
100
95%
Auxiliary Power Supply for Thermistor Applications
Attribute
Output voltage
Output current
Embedded RTC
Attribute
Resolution
Accuracy, typical
Supercap life, typical
Expected Duty Cycle
Minimum
Maximum
9.50%
16.25%
19.50%
26.25%
39.50%
46.25%
54.50%
61.25%
64.50%
71.25%
84.50%
91.25%
94.50%
100.00%
4.00%
17.50%
9.00%
22.50%
19.00%
32.50%
39.00%
52.50%
54.00%
67.50%
64.00%
77.50%
84.00%
97.50%
94.00%
100.00%
3.00%
30.00%
8.00%
35.00%
18.00%
45.00%
38.00%
65.00%
53.00%
80.00%
63.00%
90.00%
83.00%
100.00%
93.00%
100.00%
Value
9.5V, min
10.04V, typical
10.5V, max
10 mA, typical
20 mA, max
Value
1 sec
± 60 sec/month @ 25 °C
5 years @ 40 °C, 14.5 years @ 25 °C
Specifications
Chapter A
Typical Duty Cycle
(1.27 KΩ load)
%Duty Cycle
12.3
22.4
42.3
57.3
67.3
87.3
97.0
9.7
14.8
24.7
44.7
59.6
69.6
89.5
98.1
14.7
19.5
29.6
49.3
64.0
73.8
92.4
98.0
135

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents