Allen-Bradley 2080-LC20-20QBB User Manual page 154

Micro820 series programmable controllers
Hide thumbs Also See for 2080-LC20-20QBB:
Table of Contents

Advertisement

Appendix B
Troubleshooting
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
0xF023
Non-
The controller program has been cleared. This
recoverable
happened because:
• a power down occurred during program
• the Flash Integrity Test failed (Micro810 only).
0xF030
Recoverable Power down information in persistent memory
may not be written properly due to a noisy
0xF031
environment or an internal hardware failure.
0xF032
If the system variable
0xF033
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
0xF050
Recoverable The embedded I/O configuration in the user
program is invalid.
0xF100
Recoverable There is general configuration error detected in
the motion configuration downloaded from the
Connected Components Workbench software,
such as number of axis, or motion execution
interval being configured out of range.
0xF110
Recoverable There is motion resource missing, such as
Motion_DIAG variable not defined.
(1)
0xF12z
Recoverable Motion configuration for axis z cannot be
supported by this controller model, or the axis
configuration has some resource conflict with
some other motion axis, which has been
configured earlier.
(1)
0xF15z
Recoverable There is a motion engine logic error (firmware
logic issue or memory crash) for one axis
detected during motion engine cyclic operation.
One possible reason can be motion engine data/
memory crash.
0xF210
Recoverable The expansion I/O terminator is missing.
0xF230
Recoverable The maximum number of expansion I/O modules
has been exceeded.
0xF250
Recoverable There is a non-recoverable error and the
expansion I/O module(s) could not be detected.
(2)
0xF26z
Recoverable An expansion I/O master fault is detected on the
system.
144
download or transfer from the memory
module.
Recommended Action
Perform one of the following:
• See
Corrective Actions for Non-recoverable Faults on page
• Download or transfer the program.
See
Corrective Actions for Recoverable Faults on page
See
Corrective Actions for Recoverable Faults on page
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Correct the axes configuration in the user program.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Correct the axes configuration in the user program.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Remove all axes and re-configure motion with the guidance from
the User Manual.
See
Corrective Actions for Recoverable Faults on page
Perform the following:
1. Power off the controller.
2. Attach the expansion I/O terminator on the last expansion I/O
module on the system.
3. Power on the controller.
4. See
Corrective Actions for Recoverable Faults on page
Perform the following:
1. Power off the controller.
2. Check that the number of expansion I/O modules is not more than
four.
3. Power on the controller.
4. See
Corrective Actions for Recoverable Faults on page
See
Corrective Actions for Recoverable Faults on page
See
Corrective Actions for Recoverable Faults on page
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018