Allen-Bradley 2080-LC20-20QBB User Manual page 143

Micro820 series programmable controllers
Hide thumbs Also See for 2080-LC20-20QBB:
Table of Contents

Advertisement

Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
DC Output Specifications for 2080-LC20-20QBB(R)
Attribute
Current ratings per point
Surge current per point
peak current
max surge duration
max rate of repetition @ 30 °C
max rate of repetition @ 65 °C
Controller current, max total
Turn-on time, max
Turn-off time, max
Response time, max
Frequency rate
(1) High speed output operation is greater than 5 Khz.
PWM Output Duty Cycle Error
Turn On/Off time for the Micro820 controllers for the PWM output port is
0.2 µs and 2.5 µs max, respectively. Duty cycle error is:
Positive error = 2.5 µs * F
Negative error = -0.2 µs * F
The plot below shows duty cycle error vs. frequency.
To get the duty cycle error at a certain frequency, for example, the user sets
frequency to 20 kHz, and sets duty cycle to 30% in Connected Components
Workbench, then actual duty cycle is
+5%
30%
-0.4%.
Specifications
Standard Outputs
High Speed Output
(Outputs O-00...O-05)
(Output O-06)
0.3 A @ 65 °C, max
100 mA (high speed
1.0 A @ 30 °C, max
operation)
1.0 mA, max leakage
1.0 A @ 30 °C
0.3 A @ 65 °C
(standard operation)
1.0 mA, max leakage
4.0 A
10 ms
once each second
once every two seconds
3 A
0.2 µs
0.1 ms
2.5 µs
1.0 ms
10 ms
NA
2%
Chapter A
(1)
133