Allen-Bradley 2080-LC20-20QBB User Manual page 156

Micro820 series programmable controllers
Hide thumbs Also See for 2080-LC20-20QBB:
Table of Contents

Advertisement

Appendix B
Troubleshooting
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
(3)
0xF0Az
Recoverable The plug-in I/O module experienced an error
during operation.
(3)
0xF0Bz
Recoverable The plug-in I/O module configuration does not
match the actual I/O configuration detected.
(3)
0xF0Dz
Recoverable When power was applied to the plug-in I/O
module or the plug-in I/O module was removed, a
hardware error occurred.
(3)
0xF0Ez
Recoverable The plug-in I/O module configuration does not
match the actual I/O configuration detected.
0xF830
Recoverable An error occurred in the EII configuration.
0xF840
Recoverable An error occurred in the HSC configuration.
0xF850
Recoverable An error occurred in the STI configuration.
0xF860
Recoverable A data overflow occurred.
A data overflow error is generated when the
ladder, structured text or function block diagram
execution encounters a divide-by-zero.
0xF870
Recoverable An index address was out of data space.
146
Recommended Action
Perform the following:
• Check the condition and operation of the plug-in I/O module.
• See
Corrective Actions for Recoverable Faults on page
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page
• Correct the plug-in I/O module configuration in the user program to
match that of the actual hardware configuration.
• Check the condition and operation of the plug-in I/O module.
• Replace the plug-in I/O module.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the plug-in I/O module configuration in the user program.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the plug-in I/O module configuration in the user program.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Review and change the EII configuration in the Micro800 controller
properties.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Review and change the EII configuration in the Micro800 controller
properties.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Review and change the EII configuration in the Micro800 controller
properties.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the program to ensure that there is no data overflow.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the program to ensure that there is no index used to access
an array element beyond the array boundaries.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
149.
149.
149.
149.
149.
149.
149.
149.
149.