List of Error Codes for Micro800 controllers
Error Code Fault Type Description
0xF0878
Recoverable An index used to access a bit is beyond the
boundaries of the data type it is used on.
0xF880
Recoverable A data conversion error occurred.
0xF888
Recoverable The call stack of the controller cannot support the
sequence of calls to function blocks in the current
project. Too many blocks are within another
block.
0xF898
Recoverable An error occurred in the user interrupt
configuration for the plug-in I/O module.
0xF8A0
Recoverable The TOW parameters are invalid.
0xF8A1
Recoverable The DOY parameters are invalid.
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
Recommended Action
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the program to ensure that there is no index used to access
a bit beyond the boundaries of the data type.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the program to ensure that there is no data conversion error.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Change the project to reduce the quantity of blocks being called
within a block.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page
• Correct the user interrupt configuration for plug-in I/O module in the
user program to match that of the actual hardware configuration.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
Appendix B
Troubleshooting
149.
149.
149.
149.
149.
149.
147