Allen-Bradley 2080-LC20-20QBB User Manual page 140

Micro820 series programmable controllers
Hide thumbs Also See for 2080-LC20-20QBB:
Table of Contents

Advertisement

Chapter A
Specifications
General Specifications
Attribute
Power dissipation
Power supply voltage range
Auxiliary power supply output for
thermistor
I/O rating
Isolation voltage
Pilot duty rating
Insulation stripping length
Enclosure type rating
North American temp code
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
130
2080-LC20-20AWB(R)
6 W
20.4...26.4 V DC, Class 2
10V
Input: 120V AC 16 mA
Output: 2 A, 240 V AC
2A, 24V DC
250V (continuous), Reinforced
Insulation Type, Output to Aux and
Network, Inputs to Outputs.
150V (continuous), Reinforced
Insulation Type, Input to Aux and
Network.
Type tested for 60 s @ 3250 V DC
Output to Aux and Network, Inputs
to Outputs.
Type tested for 60 s @ 1950 V DC
Input to Aux and Network.
C300, R150
7 mm for the removable and fixed terminal blocks
5 mm for the RS232/RS485 serial port
Meets IP20
T4
Analog Input Specifications for I-00...I-03
Attribute
Number of inputs
Type
Data range
Input voltage range
Maximum input
Input impedance
Resolution
Smoothing
Input time constant, typical
Isolation
Accuracy (25...55 °C)
2080-LC20-20QBB(R)
Input: 24V DC, 8.8 mA
Output:24V DC,1Aperpoint
(Surrounding air temperature
30°C)
24 V DC, 0.3
A per point (Surrounding air
temperature 65 °C)
50V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs.
Type tested for 60 s @ 720 V DC,
I/O to Aux and Network, Inputs
to Outputs.
Value
4
Voltage (single-ended)
0...4095
0...10V DC
26.4V DC
14.14 kΩ
12-bit, 2.5 mV/count
None
0.44 ms
None
5% of full-scale (2% with calibration)
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
2080-LC20-20QWB(R)
Input: 24V DC, 8.8 mA
Output: 2 A,
240 V AC, 2A, 24V DC
250V (continuous), Reinforced
Insulation Type, Output to Aux and
Network, Inputs to Outputs.
50V (continuous), Reinforced Insulation
Type, Input to Aux and Network.
Type tested for 60 s @ 720 V DC,
Inputs to Aux and Network, 3250 V DC
Outputs to Aux and Network, Inputs to
Outputs.
C300, R150