Danfoss VLT FC 102 User Manual page 40

Parallel drive modules 250–1200 kw
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Maintenance, Diagnostics, a...
Bit Hex
Alarm Word Extended Status Word
0
00000001
1
00000002
2
00000004
3
00000008
6
6
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10 00000400
11 00000800
12 00001000
13 00002000
14 00004000
15 00008000
16 00010000
17 00020000
18 00040000
38
VLT
Dec
Alarm word
Alarm word 2
1
Brake check (A28)
Servicetrip, read/
write
2
Pwr.card temp
Servicetrip,
(A69)
(reserved)
4
Earth fault (A14)
Servicetrip,
typecode/
sparepart
8
Ctrl.card temp
Servicetrip,
(A65)
(reserved)
16
Ctrl. word TO
Servicetrip,
(A17)
(reserved)
32
Overcurrent (A13)
Reserved
64
Torque limit (A12)
Reserved
128
Motor th over
Reserved
(A11)
256
Motor ETR over
Reserved
(A10)
512
Inverter overld.
Discharge high
(A9)
1024
DC under volt (A8) Start failed
2048
DC over volt (A7)
Speed limit
4096
Short circuit (A16) External
interlock
8192
Inrush fault (A33)
Illegal option
combi.
16384
Mains ph. loss (A4) No safety option Mains ph. loss
32768
AMA not OK
Reserved
65536
Live zero error
Reserved
(A2)
131072
Internal fault (A38) KTY error
262144
Brake overload
Fans error
(A26)
Danfoss A/S © 08/2017 All rights reserved.
®
Parallel Drive Modules
Warning word
Brake check (W28) Start delayed Ramping
Pwr.card temp
(A69)
Earth fault (W14)
Ctrl.card temp
(W65)
Ctrl. word TO
(W17)
Overcurrent (W13) Reserved
Torque limit (W12) Reserved
Motor th over
(W11)
Motor ETR over
(W10)
Inverter Overld
(W9)
DC under volt
(W8)
DC over volt (W7) Multi-motor
DC voltage low
(W6)
DC voltage high
(W5)
(W4)
No motor (W3)
Live zero error
(W2)
10 V low (W1)
Brake overload
(W26)
Warning
Extended
word 2
status word
Stop delayed AMA running
Reserved
Start CW/CCW
start_possible is active, when the DI
selections [12] OR [13] are active
and the requested direction
matches the reference sign
Reserved
Slow down
slow down command active, for
example via CTW bit 11 or DI
Catch up
catch up command active, for
example via CTW bit 12 or DI
Feedback high
feedback >parameter 4-57 Warning
Feedback High
Feedback low
feedback <parameter 4-56 Warning
Feedback Low
Reserved
Output current high
current >parameter 4-51 Warning
Current High
Reserved
Output current low
current <parameter 4-50 Warning
Current Low
Discharge
Output freq high
high
speed >parameter 4-53 Warning
Speed High
Multi-motor
Output freq low
underload
speed <parameter 4-52 Warning
Speed Low
Brake check OK
overload
brake test NOT OK
Compressor
Braking max.
interlock
BrakePower > Brakepowerlimit
(2-12)
Mechanical
Braking
brake sliding
Safe option
Out of speed range
warning
Auto DC
OVC active
braking
AC brake
KTY warn
Password timelock
number of allowed password trials
exceeded - timelock active
Fans warn
Password protection
0-61 = ALL_NO_ACCESS OR
BUS_NO_ACCESS OR
BUS_READONLY
MG37L202