Q3 Function Set-Ups; Control Terminal Programming; Configuring Automatic Energy Optimization; Configuring Automatic Motor Adaptation - Danfoss VLT FC 102 User Manual

Parallel drive modules 250–1200 kw
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Commissioning

4.4.2 Q3 Function Set-ups

The Function Set-up provides quick and easy access to all
parameters required for most applications. Among other
features, it also includes parameters for selecting which
variables to display on the LCP, digital preset speeds,
scaling of analog references, closed loop single-zone and
multi-zone applications, and functions specifically related
to the applications. For more on Function Set-up, including
programming examples, refer to the operating instructions
and programming guides applicable to the VLT
®
Drive FC 102, VLT
AQUA Drive FC 202, or VLT
AutomationDrive FC 301/FC 302 series of VLT
Drive Modules used in the drive system.

4.4.3 Control Terminal Programming

The control terminals can be programmed using the LCP.
Each terminal has specified functions it can
perform.
Parameters associated with the terminal enable
the function.
For proper drive system functioning, the control
terminals must be:
-
Wired properly.
-
Programmed for the intended function.
-
Receiving a signal.
See Table 8.2 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in parameter 0-03 Regional Settings).
The following example shows how terminal 18 is accessed
to see the default setting:
1.
Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out Parameter Data Set and
then press [OK].
14.6%
Main Menu
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
Illustration 4.4 Main Menu Display Example
2.
Scroll to parameter group 5-1* Digital Inputs and
then press [OK].
MG37L202
User Guide
®
HVAC
®
®
Parallel
4.4.4 Configuring Automatic Energy
Automatic energy optimization (AEO) is a procedure that
minimizes voltage to the motor, reducing energy
consumption, heat, and noise.
0.00A
1(1)
4.4.5 Configuring Automatic Motor
Automatic motor adaptation (AMA) is a procedure that
optimizes compatibility between the drive system and the
motor.
During this procedure, the drive system builds a
mathematical model of the motor for regulating output
motor current. The procedure also tests the input phase
Danfoss A/S © 08/2017 All rights reserved.
14.7%
Digital In/Out
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
Illustration 4.5 Parameter Group Display Example
3.
Scroll to parameter 5-10 Terminal 18 Digital Input.
Press [OK] to access function options. The default
setting Start is displayed. If this terminal must be
reprogrammed, the LCP can be used to access
the options available for this parameter and then
select a different value.
14.7%
Digital Inputs
5-10 Terminal 18 Digital
Input
[8]] Start
Illustration 4.6 Function Choice Display Example
Optimization
1.
Press [Main Menu].
2.
Select 1-** Load and Motor and press [OK].
3.
Select 1-0* General Settings and press [OK].
4.
Select parameter 1-03 Torque Characteristics and
press [OK].
5.
Select either [2] Auto Energy Optim CT or [3] Auto
Energy Optim VT and press [OK].
Adaptation
0.00A
1(1)
5-**
4
0.00A
1(1)
5-1*
19
4

Advertisement