Specifications
7 Specifications
7.1 Power-dependent Specifications
7.1.1 VLT
®
Power range
Drive modules
Rectifier configuration
High/normal load
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Protection rating
Efficiency
Output frequency [Hz]
7
7
Heat sink overtemperature trip [°C (°F)]
Power card ambient trip [°C (°F)]
Output current [A]
Continuous (at 380–440 V)
Intermittent (60 s overload) at 400 V
Continuous (at 460/500 V)
Intermittent (60 s overload) at 460/500 V
Continuous (at 400 V) [kVA]
Continuous (at 460 V) [kVA]
Continuous (at 500 V) [kVA]
Input current [A]
Continuous (at 400 V)
Continuous (at 460/500 V)
Power losses [W]
Drive modules at 400 V
Drive modules at 460 V
AC busbars at 400 V
AC busbars at 460 V
DC busbars during regeneration
Maximum cable size [mm
1)
Mains
Motor
Brake
Regeneration terminals
Maximum external mains fuses
6-pulse configuration
12-pulse configuration
Table 7.1 FC 102, 380–480 V AC Mains Supply (2-module System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
54
HVAC Drive FC 102
2
(mcm)]
Danfoss A/S © 08/2017 All rights reserved.
®
VLT
Parallel Drive Modules
N315
N355
2
2
12-pulse
NO
NO
315
355
450
500
588
658
647
724
535
590
588
649
407
456
426
470
463
511
567
647
516
580
5825
6110
4998
5964
550
555
548
551
93
95
4x120 (250)
4x120 (250)
4x70 (2/0)
4x120 (250)
–
–
700 A, 600 V
N400
N450
2
2
NO
NO
400
450
600
600
IP00
0.98
0–590
110 (230)
80 (176)
745
800
820
880
678
730
746
803
516
554
540
582
587
632
733
787
667
718
7069
7538
6175
6609
561
565
556
560
98
101
4x95 (3/0)
4x150 (300)
6x120 (250)
–
–
N500
2
6-pulse/12-pulse
NO
500
700/650
880
968
780
858
610
621
675
875
759
8468
7140
575
563
105
4x150 (300)
4x150 (300)
600 V, 1600 A
–
MG37L202
Need help?