Application Set-up Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
29
D IN
D IN
32
D IN
33
5
5
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 5.12 Start/Stop with Reversing and 4 Preset Speeds
5.2.7 External Alarm Reset
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 5.13 External Alarm Reset
28
®
VLT
Parallel Drive Modules
Parameters
Function
Setting
Parameter 5-10 Terminal
[8] Start
18 Digital Input
Parameter 5-11 Terminal
[10]
19 Digital Input
Reversing*
Parameter 5-12 Terminal
[0] No
27 Digital Input
operation
Parameter 5-14 Terminal
[16] Preset
32 Digital Input
ref bit 0
Parameter 5-15 Terminal
[17] Preset
33 Digital Input
ref bit 1
Parameter 3-10 Preset
Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
* = Default value
Notes/comments:
Parameters
Function
Setting
Parameter 5-11 T
[1] Reset
erminal 19
Digital Input
* = Default value
Notes/comments:
Danfoss A/S © 08/2017 All rights reserved.
5.2.8 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
To meet PELV insulation requirements, use only
thermistors with reinforced or double
insulation.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 5.14 Motor Thermistor
Parameters
Function
Setting
Parameter 1-90
[2] Thermistor
Motor Thermal
trip
Protection
Parameter 1-93 T
[1] Analog
hermistor
input 53
Resource
* = Default value
Notes/comments:
If only a warning is needed, set
parameter 1-90 Motor Thermal
Protection to [1] Thermistor
warning.
MG37L202