Commissioning
Perform automated initialization as follows:
1.
Press [Main Menu] twice to access the
parameters.
2.
Go to parameter 14-22 Operation Mode and then
press [OK].
3.
Scroll to Initialization and then press [OK].
4.
Remove power from the drive system and wait
4
4
for the display to turn off.
5.
Apply power to the drive system.
Default parameter settings are restored during
startup. As a result, startup takes slightly longer
than normal.
6.
Alarm 80 is shown.
7.
Press [Reset].
Manual initialization
Manual initialization erases all motor, programming, locali-
zation, and monitoring data before restoring factory
default settings. It does not, however, reset the following
information:
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Perform manual initialization as follows:
1.
Remove power from the drive system and wait
for the display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK]
simultaneously while applying power to the unit.
Hold approximately 5 s or until an audible click is
heard and the drive system's cooling fan starts.
Factory default parameter settings are restored during
startup. As a result, startup takes slightly longer than
normal.