Specifications
Mode select
Voltage mode
Voltage level
Input resistance, R
i
Max. voltage
Current mode
Current level
Input resistance, R
i
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Illustration 8.1 PELV Isolation of Analog Inputs
Analog output
Number of programmable analog outputs
Terminal number
Current range at analog output
Max. resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
®
VLT
AQUA Drive FC 202 Operating Instructions
PELV isolation
+24V
Control
18
High
voltage
37
Functional
isolation
RS485
MG20MA02 - Rev. 2013-10-29
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
0 to +10 V (scaleable)
Switch S201/switch S202 = ON (I)
0/4 to 20 mA (scaleable)
Max. error 0.5% of full scale
Mains
Motor
DC-Bus
Max. error: 0.8% of full scale
18, 19, 27
approx. 10 kΩ
±20 V
approx. 200 Ω
30 mA
10 bit (+ sign)
200 Hz
8
8
1
42
0/4-20 mA
500 Ω
8 bit
4 (6)
1)
, 29
1)
, 32, 33,
PNP or NPN
0-24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
approx. 4 kΩ
2
1)
27, 29
0-24 V
40 mA
1 kΩ
10 nF
53