Reactor e-30i series; reactor e-xp2i series; electric, heated, integrated plural component proportioning system with integrated generator
Table of Contents

Advertisement

Error
Error
Type
Code
Position
WMCE MCM
ALARM
WSCX ADM
ADVISORY Invalid CAN
WSUX USB
ADVISORY USB Invalid
WXUD ADM
ADVISORY USB Download
WXUU ADM
ADVISORY USB Upload Error Custom language file
WX00
MCM
ALARM
3A1705E
Name
Cause
Load Center Fault
Bad Connection between
MCM (Port 2) and load
center board.
Bad load center.
Duplicate node on CAN
Configuration
network.
A valid configuration file
Configuration
can't be found for the
USB.
Bad ADM.
Log Download Failed.
Error
failed to upload
External Input
The alarm external input
has been driven low.
Troubleshooting
Solution
Check connection and
cables.
Replace load center. See
System Repair manual.
Verify LPTCM are set to A
and B.
Insert a system token into
the ADM and cycle the
power. Wait until the lights
on USB port stop flashing
before Removing the token.
Replace ADM. See System
Repair manual.
Backup and reformat the
USB drive. Retry download.
Perform normal USB
download and use the new
disptext.txt file to upload the
custom language.
An active alarm is being
generated by the external
trigger. If the external alarm
is not configured check for a
short in the wiring going to
MCM port 7, pins 1 and 3.
85