Product Overview; Use Of The Relay; Features - ABB REF 610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS755310
3.
3.1.
3.2.
Feeder Protection Relay
Technical Reference Manual

Product overview

Use of the relay

The feeder protection relay REF 610 is a versatile multifunction protection relay
mainly designed to protectincoming and outgoing feeders in a wide range of feeder
applications.
The relay is based on a microprocessor environment. A self-supervision system
continuously monitors the operation of the relay.
The HMI includes a liquid crystal display (LCD) which makes the local use of the
relay safe and easy.
Local control of the relay via serial communication can be carried out with a
computer connected to the front communication port. Remote control can be carried
out via the rear connector connected to the control and monitoring system through
the serial communication bus.

Features

Three-phase non-directional overcurrent protection with definite-time or IDMT
*
characteristic, low-set stage.
Three-phase non-directional overcurrent protection, high-set stage
*
Three-phase non-directional overcurrent protection, instantaneous stage
*
Non-directional earth-fault protection with definite-time or IDMT characteristic,
*
low-set stage
Non-directional earth-fault protection, high-set stage.
*
Phase discontinuity protection
*
Three-phase thermal overload protection for cables
*
Arc protection:
*
Two lens sensors for arc detection (optional)
*
Automatic reference level adjustment based on backlight intensity
*
Arc detection via a remote light signal
*
Automatic reclosing 1...3 shots
*
Circuit-breaker failure protection
*
Trip counters for circuit-breaker condition monitoring
*
Trip-circuit supervision with possibility to route the warning signal to a signal
*
output
Trip lockout function
*
Four accurate current inputs
*
User-selectable rated frequency 50/60 Hz
*
Three normally open power output contacts
*
Two change-over signal output contacts and three additional change-over signal
*
output contacts on the optional I/O module
Output contact functions freely configurable for wanted operation
*
REF 610
REF 610
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents