ABB REF 610 Technical Reference Manual page 98

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
Table 5.1.15.1.-14 Fault record
Address
Signal name
601
Latest selection code
602
Sequence number
603
Unread records left
604
Time stamp of the recorded data, date
605
Time stamp of the recorded data, date and time
606
Time stamp of the recorded data, time
607
Time stamp of the recorded data, time
608
Phase current I
609
Phase current I
610
Phase current I
611
Earth-fault current
612
Phase discontinuity
613
Thermal level at start
614
Thermal level at trip
615
Maximum pickup phase current I
616
Maximum pickup phase current I
617
Maximum pickup phase current I
618
Maximum pickup earth-fault current
619
Start duration of stage I>
620
Start duration of stage I>>
621
Start duration of stage I>>>
622
Start duration of stage I
623
Start duration of stage I
Start duration of stage ΔI>
624
625
Start duration of external trip
626
Trip number of AR sequence
627
Start duration of stage ARC (local)
628
Start duration of stage ARC (remote)
a)
Readable and writeable register.
Table 5.1.15.1.-15 Event record
Address
Signal name
671
Latest selection code
672
Sequence number
98
Feeder Protection Relay
Technical Reference Manual
a)
L1
L2
L3
L1
L2
L3
>
0
>>
0
Structure 3
This structure contains Modbus event records. Refer to Event records earlier in this
section for the reading method.
a)
Range
Comment
1...2
1 = read oldest unread record
2 = read oldest stored record
1...255
0...6
2 bytes: YY.MM
2 bytes: DD.HH
2 bytes: MM.SS
0...999
0...999 ms
0...5000
0...50 x I
n
0...5000
0...50 x I
n
0...5000
0...50 x I
n
0...20000
0...2000% I
0...100
0...100%
0...106
0...106%
0...106
0...106%
0...5000
0...50 x I
n
0...5000
0...50 x I
n
0...5000
0...50 x I
n
0...20000
0...2000% I
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0/100
0/100%
0...255
0/100
0/100%
0/100
0/100%
Range
Comment
1...3
1 = read oldest unread record
2 = read oldest stored record
3 = clear Modbus event buffer
-1...-99
-1...-99 = move to the nth
newest record
1...255
1MRS755310
n
n

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents