ABB REF 610 Technical Reference Manual page 164

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
164
Feeder Protection Relay
Technical Reference Manual
Variable
Checksum, SGF 5
Checksum, SGB 1
Checksum, SGB 2
Checksum, SGB 3
Checksum, SGB 4
Checksum, SGB 5
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Checksum, SGR 7
Checksum, SGR 8
Checksum, SGL 1
Checksum, SGL 2
Checksum, SGL 3
Checksum, SGL 4
Checksum, SGL 5
Checksum, SGL 6
Checksum, SGL 7
Checksum, SGL 8
Table 8.-2
Setting group 2
Variable
Start value of stage I>
Operate time of stage I>
Time/current characteristic for
stage I>
Time multiplier k
Time multiplier n
Resetting time of stage I>
Start value of stage I>>
Operate time of stage I>>
Start value of stage I>>>
Operate time of stage I>>>
Start value of stage I
>
0
Operate time of stage I
>
0
Time/current characteristic for
stage I
>
0
Time multiplier k
0
Group/
Setting
Channel
range
1 (R, W,
P)
1S65
0...255
1S71
0...1048575
1S72
0...1048575
1S73
0...1048575
1S74
0...1048575
1S75
0...1048575
1S81
0...8388607
1S82
0...8388607
1S83
0...8388607
1S84
0...8388607
1S85
0...8388607
1S86
0...8388607
1S87
0...8388607
1S88
0...8388607
1S91
0...8388607
1S92
0...8388607
1S93
0...8388607
1S94
0...8388607
1S95
0...8388607
1S96
0...8388607
1S97
0...8388607
1S98
0...8388607
Group/
Setting range
Channel 2
(R, W, P)
2S1
0.30...5.0 x I
2S2
0.05...300 s
2S3
0...9
2S4
0.05...1.00
2S5
1.0...15.0
2S6
0.05...2.50 s
2S7
0.50...35.0 x I
2S8
0.04...300 s
2S9
0.50...35.0 x I
2S10
0.04...30.0 s
2S11
1.0...100% I
2S12
0.05...300 s
2S13
0...9
2S14
0.05...1.00
1MRS755310
Default
Custo-
setting
mer's
setting
0
0
0
0
0
0
2108074
2108074
2108074
5461
5461
0
0
0
0
0
0
0
0
0
0
0
Default
Custo-
setting
mer's
setting
0.30 x I
n
n
0.05 s
0
0.05
1.0
0.05 s
0.50 x I
n
n
0.04 s
0.50 x I
n
n
0.04 s
1.0% I
n
n
0.05 s
0
0.05

Hide quick links:

Advertisement

Table of Contents
loading