ABB REF 610 Technical Reference Manual page 116

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
116
Feeder Protection Relay
Technical Reference Manual
Recorded data
Parameter (R)
Trip indication
code
Number of starts of
stage I>
Number of starts of
stage I>>
Number of starts of
stage I>>>
Number of starts of
stage I0>
Number of starts of
stage I0>>
Value
64=I
>>
L1
128=I
>>
0
256=I
>>>
L3
512=I
>>>
L2
1024=I
>>>
L1
2048=ΔI>
4096=θ>
8192=external trip
16384=AR
32768=trip of stage ARC (local)
65536=trip of stage ARC (remote)
0 = —
V2
1=start of stage I>
2=trip of stage I>
3=start of stage I>>
4=trip of stage I>>
5=start of stage I>>>
6=trip of stage I>>>
7=start of stage I
8=trip of stage I
9=start of stage I
10=trip of stage I
11=start of stage ΔI>
12=trip of stage ΔI>
13=alarm of stage θ>
14=trip of stage θ>
15=external trip
16=definite trip alarm
17=CB reclosing failed
18=AR shot due
19=AR lockout
20=trip of stage ARC
21=CBFP
V3
0...999
V4
0...999
V5
0...999
V6
0...999
V7
0...999
1MRS755310
>
0
>
0
>>
0
>>
0