REF 610
REF 610
Description
a)
Store counter
Remote control of setting group
Entering the SPA password for settings
Changing the SPA password or taking the
password protection into use
Changing the HMI Setting password
Changing the HMI Communication password
Clearing trip counters or AR counter
Restoring factory settings
Warning code
IRF code
Unit address of the relay
Data transfer rate (SPA), kbps
Rear communication
Rear communication protocol
Connection type
Line-idle state
Optional communication module
CPU software number
CPU software revision
CPU build number
DNP protocol name
DNP software number
DNP software revision
DNP build number
Relay serial number
CPU serial number
DNP serial number
Test date
Date reading and setting
(RED 500 format)
Time reading and setting
(RED 500 format)
a)
The store counter can be used for monitoring parameter changes, for instance. The store counter is incremented by one on each parameter
change via the HMI or serial communication. When the counter reaches its maximum value, it will roll over. If the factory settings are restored,
the counter is cleared.
b)
In case of a warning, the value 255 is stored in V169. This enables the master to continuously read only V169.
122
Feeder Protection Relay
Technical Reference Manual
Parameter
V114
V150
V160
V161
V162
V163
V166
V167
V168
V169
V200
V201
V202
c)
V203
V204
V205
V206
V227
V228
V229
2V226
2V227
2V228
2V229
V230
V231
V232
V235
V250
V251
R, W, P
Value
R
0...65535
R, W
0 = Setting group 1
1 = Setting group 2
W
1...999
W (P)
1...999
W
1...999
W
1...999
W (P)
1 = Clear trip counters
2 = Clear AR counters
W (P)
2 = Restore factory settings for CPU
3 = Restore factory settings for DNP
b)
R
0...63
b)
R
0...255
R, W
1...254
R, W
9.6/4.8
W
1 = Rear connector activated
R, W
0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
4 = DNP 3.0 (read-only)
R, W
0 = Loop
1 = Star
R, W
0 = Light off
1 = Light on
R, W (P)
0 = Not in use
d)
1 = In use
R
1MRS118512
R
A...Z
R
XXX
R
DNP 3.0
R
1MRS118531
R
A...Z
R
XXX
R
BAxxxxxx
R
ACxxxxxx
R
AKxxxxxx
R
YYMMDD
R, W
YY-MM-DD
R, W
HH.MM;SS.sss
1MRS755310