ABB REF 610 Technical Reference Manual page 129

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS755310
Feeder Protection Relay
Technical Reference Manual
Table 5.1.17.1.-2
Event codes E1...E4 and E7
Channel
Event
Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
0
E7
The thermal level has been changed via serial communication
Table 5.1.17.1.-3
Event codes E50...E51
Channel
Event
Description
0
E50
Relay restart
0
E51
Event buffer overflow
Events possible to mask out:
Table 5.1.17.1.-4
Event codes E31...E36
Channel
Event
Description
0
E31
Disturbance recorder triggered
0
E32
Disturbance recorder memory cleared
0
E33
HMI Setting password opened
0
E34
HMI Setting password closed
0
E35
HMI Communication password opened
0
E36
HMI Communication password closed
Default value of event mask V155
Channel 1
Table 5.1.17.1.-5
Event codes E1...E12
Channel
Event
Description
1
E1
Start signal from stage I> activated
1
E2
Start signal from stage I> reset
1
E3
Trip signal from stage I> activated
1
E4
Trip signal from stage I> reset
1
E5
Start signal from stage I>> activated
1
E6
Start signal from stage I>> reset
1
E7
Trip signal from stage I>> activated
1
E8
Trip signal from stage I>> reset
1
E9
Start signal from stage I>>> activated
1
E10
Start signal from stage I>>> reset
1
E11
Trip signal from stage I>>> activated
1
E12
Trip signal from stage I>>> reset
Default value of event mask 1V155
REF 610
REF 610
Weighting
Default
factor
value
1
1
2
0
4
0
8
0
16
0
32
0
1
Weighting
Default
factor
value
1
1
2
0
4
1
8
0
16
1
32
0
64
1
128
0
256
1
512
0
1024
1
2048
0
1365
129

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents