ABB REF 610 Technical Reference Manual page 143

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS755310
Feeder Protection Relay
Technical Reference Manual
module. The termination resistor is selected by setting jumper X5 to the ON
position. If the internal termination resistor of 120 Ω is used, the impedance of the
cable should be the same.
The bus is to be biased at one end to ensure fail-safe operation, which can be done
using the pull-up and pull-down resistors on the communication module. The pull-
up and pull-down resistors are selected by setting jumpers X3 and X4 to the ON
position.
The jumpers have been set to no termination (X5 in the OFF position) and no
biasing (X3 and X4 in the OFF position) as default.
Fig. 5.2.3.-1
Jumper location on the RS-485 communication module
Table 5.2.3.-2
RS-485 rear connector
Terminal
Function
X5.5-6
Data A (+)
X5.5-5
Data B (-)
X5.5-4
Signal GND (for potential balancing)
X5.5-3
-
X5.5-2
Shield GND (via capacitor)
X5.5-1
Shield GND
off
X3
on
off
X4
on
off
X5
on
REF 610
REF 610
A040334
143