ABB REF 610 Technical Reference Manual page 42

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
42
Feeder Protection Relay
Technical Reference Manual
β
[ ]
=
×
t s
k
α
I
1
>
I
t
= operate time
I
= phase (or earth-fault) current value
k (or k
)
= time multiplier
0
I> (or I
>)
= set start value
0
The actual operate time of the relay (see Fig. 5.1.4.9.-1...Fig. 5.1.4.9.-
4), includes an additional filter and detection time, and the operate time
of the trip output contact. When the operate time of the relay is
calculated as above, approximately 30 ms should be added to the
result.
Values of constants α and β
Table 5.1.4.9.-2
Time/current curve group
Normal inverse
Very inverse
Extremely inverse
Long-time inverse
According to the standard, the normal current range is 2...20 times the set start value
at normal inverse, very inverse or extremely inverse characteristic. The relay is to
start before the current exceeds the set start value by 1.3 times. At long-time inverse
characteristic, the normal current range is specified to be 2...7 times the set start
value, and the relay is to start before the current exceeds the set start value by 1.1
times
Table 5.1.4.9.-3
Operate time tolerances specified by the standard
a)
I/I>
2
5
7
10
20
a)
or I
/I
>
0
0
b)
E = accuracy in percent; - = not specified
Within the normal current range the inverse-time stage fulfils the tolerance
requirements of class 5 at all degrees of inversity.
α
0.02
1.0
2.0
1.0
b)
b)
Normal
Very
2,22E
2,34E
1,13E
1,26E
-
-
1,01E
1,01E
1,00E
1,00E
1MRS755310
(4)
β
0.14
13.5
80.0
120
b)
b)
Extremely
Long time
2,44E
2,34E
1,48E
1,26E
-
1,00E
1,02E
-
1,00E
-